Технические данные PDF

Краткое описание: технические характеристики  VBA-4E4E-G12-ZAJ

Описание оборудования
G12 flat module
2 x 4 inputs (PNP)
General specifications
Slave typeDouble A/B slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd60 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED PWR/FAULT2 Dual LEDs green/red
green: AS-Interface voltage
red: Communication error
yellow/red flashing: Address 0
green/red flashing: Sensor supply overload
LED INswitching state (input); 8 LED yellow
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 80 mA (without sensors) / max. 280 mA
Protection classIII
Surge protectionUe: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Input
Number/Type2x 4 inputs for 2- or 3-wire sensors (PNP), DC
alternative 2x 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 6 mA
Signal delay< 1 ms (input/AS-Interface)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Programming instructions
ProfileS-0.A.2
IO code0
ID codeA
ID1 codeSlave 1 Slave 2
1 2
ID2 code2
Data bits (function via AS-Interface)Input slave 1 input slave 2
D0IN1.1 IN2.1
D1IN1.2 IN2.2
D2IN1.3 IN2.3
D3IN1.4 IN2.4
Parameter bits (programmable via AS-i)function
P0not used
P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree3
Mechanical specifications
Degree of protectionIP67
Connectioncable piercing method
flat cable yellow
inputs: M12 round connector
Material
HousingPBT
Mass230 g
Tightening torque, cable gland0.4 Nm
MountingMounting plate
Оформить заказ на VBA-4E4E-G12-ZAJ вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.