Технические данные PDF

Краткое описание: технические характеристики  VBA-4A-G11-I/U-F

Описание оборудования
G11 analog module
4 analog outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd220 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGStatus of output signal; yellow LED
Yellow: Output value within range
Yellow flashing: lead breakage (on current output) or output value out of range
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display output supply; LED green
green: output supply from AS-Interface
off: output supply from auxiliary voltage
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 75 mA (without outputs) / max. 200 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Output
Number/Type4 analog outputs
Current: 0 ... 20 mA
Voltage: 0 ... 10 V
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Loadvoltage output: min. 1 kΩ
current output: max. 600 Ω
Current loading capacity≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected
≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected
ResolutionVoltage output: 3 mV
Current output: 6 µA
Accuracy0.15 % of full-scale value
Temperature influence1 µA/K or 0,3 mV/K
Short-circuit currentvoltage output: max. 22 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.6
IO code7
ID code3
ID1 codeF
ID2 code6
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0Watchdog:
P0=1 (default), watchdog active
P0=0, watchdog inactive
P1Output mode:
P1=1 (default), 4x current output
P2=0, 4x voltage output
P2Indication of peripheral fault:
P2=1 (default), peripheral fault is reported
P2=0, peripheral fault is not reported
P3Automatic mode:
P3=1 (default), manual setting of output mode
P3=0, automatic load detection (mixed mode possible)
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black
Outputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
MountingMounting plate
Оформить заказ на VBA-4A-G11-I/U-F вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.