Технические данные PDF

Краткое описание: технические характеристики  VBA-2E-G4-I

Описание оборудования
G4 module IP65
2 analog inputs (current)
General specifications
Slave typeStandard slave
AS-Interface specificationV2.1
Required master specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd160 a at 30 °C
Indicators/operating means
LED FAULTerror display; LED red
red: communication error
red flashing: peripheral error
LED PWRAS-Interface voltage; LED green
LED ANALOGstatus input signal; LED green
off: 1 < 1 mA (peripheral error)
green: 1 mA ≤ I ≤ 1 23 mA
green flashing: I > 23 mA (peripheral error)
LED AUXext. auxiliary voltage UAUX ; LED green
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 80 mA
Protection classIII
Input
Number/Type2 analog inputs (currrent), 4 ... 20 mA
Supplyfrom AS-Interface or from external auxiliary voltage as required UAUX
Current loading capacity≤ 200 mA from AS-Interface
≤ 500 mA from external auxiliary voltage UAUX
Input resistance50 Ω
Resolution16 Bit / 1 µA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileS-7.3.D
IO code7
ID code3
ID2 codeD
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0mains power frequency filter
P0=1, 50 Hz filter active
P0=0, 60 Hz filter active
P1projecting of the 2nd channel
P1=1, channel 2 is projected
P1=0, channel 2 is not projected
P2Message of peripheral error
P2=1, peripheral error is reported
P2=0, peripheral error is not reported
P3not used
Ambient conditions
Ambient temperature0 ... 70 °C (32 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP65
Connectioncable piercing method or terminal compartment
yellow flat cable/black flat cable or standard round cable
inputs/outputs: 2 x M16 x 1.5 cable glands and cage tension spring terminals, 1 x M12 x 1.5 cable gland (not used)
Material
HousingPA 6 GF30
Mass350 g
MountingDIN mounting rail
Оформить заказ на VBA-2E-G4-I вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.
Вам может понравиться