VBA-2E-G10-ZEJ-0,1M-2V3-G
Артикул: 303047
AS-Interface compact module
5 132 Р
Производитель:
PEPPERL+FUCHS
Поделиться:
Производитель: PEPPERL+FUCHS
Краткое описание: технические характеристики VBA-2E-G10-ZEJ-0,1M-2V3-G
Описание оборудования | ||
---|---|---|
G10 ultra compact module 2 inputs, 2 x M8 socket |
General specifications | ||
---|---|---|
Slave type | A/B slave | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V2.0 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
Functional safety related parameters | ||
MTTFd | 555 a | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
|
LED AS-i | AS-Interface voltage; LED green | |
LED IN | switching state (input); 2 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 18.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA (without sensors) / max. 120 mA | |
Protection class | III | |
Input | ||
Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC | |
Supply | from AS-Interface | |
Voltage | 21 ... 31 V | |
Current loading capacity | 75 mA at TB ≤ 40 °C (104 °F) 60 mA at TB ≤ 75 °C (167 °F) overload and short-circuit resistant |
|
Input current | ≤ 9 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 3 mA | |
1 (attenuated) | ≥ 5 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-0.A.2 | |
IO code | 0 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 2 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
P3 | not used | |
Approvals and certificates | ||
UL approval | cULus Listed, Type 1 enclosure | |
Maximum permissible ambient temperature | max. 65 °C (max. 149 °F) | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
|
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Mechanical specifications | ||
Degree of protection | IP67 IP67 / IP68 / IP69K with flat cable VAZ-FK-S-* |
|
Connection | AS-Interface: AS-Interface flat cable Inputs & matching connector: M8 round connector, 4-pin, A-coded, according to IEC 61076-2-104 |
|
Material | ||
Contacts | CuSn / Au | |
Housing | PBT PC | |
Body | black PUR | |
Cable | PUR | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Cable | ||
Sheath diameter | ∅4,3 mm | |
Color | black | |
Cores | 3 x 0.34 mm2 | |
Length | 0.1 m | |
Mass | 100 g | |
Tightening torque, fastening screws | 1.65 Nm | |
Tightening torque, cable gland | 0.4 Nm |