Технические данные PDF

Краткое описание: технические характеристики  VAS-2A-K12-U-S1 SIMON

Описание оборудования
Safety Monitor, 2 integrated safe outputs
General specifications
AS-Interface specificationV2.1
Switch-on delay< 10 s
Response delay< 50 ms
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd389 a
B10d2 E+5
Indicators/operating means
LED greenOff: contacts of the safety output (OSSD) open
constantly lit: contacts of the safety output (OSSD) closed
flashing: delay time running for Stop Category 1
LED yellowoff: -
constantly lit: startup/restart lock active
flashing: external test required
LED redOff: contacts of the safety output (OSSD) closed
constantly lit: contacts of the safety output (OSSD) open
flashing: error
LED POWERfrom: no power supply
green, continuous illuminated: AS-Interface power supply available
LED AS-ifrom: normal operation
red, continuous illuminated: communication error
Electrical specifications
Rated operating voltage24 V DC ± 15 %
Residual ripple ≤ 15 %
26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 200 mA
≤ 45 mA from AS-Interface
Surge protectionovervoltage category III
for rated operating voltage 300 V DC acc. to VDE 0110 Part 1
Interface
Interface typeRS 232, serial
Transfer rate9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits
Input
Number/Type2 opto-coupling inputs (high-active) "Start" and "protection control (EDM)", input currents about 10 mA at 24 V DC
Output
Safety output2 x 2 potential-free NO contacts,
max. contact loading:
1 A DC-13 at 24 V DC,
3 A AC-15 at 230 V AC
Output typeSignal output:
PNP transistor output, 200 mA, short-circuit and reverse-polarity-proof
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2006, EN 61000-6-4:2007
Low voltage
Directive 2006/95/ECEN 60947-5-1:2005
Machinery Directive
Directive 2006/42/ECEN 954-1:1996, EN 61496:2005, EN 60204-1:2006
Standard conformity
Degree of protectionEN 60529:2000
Electrical safetyEN 50178:1998
AS-InterfaceEN 62026-2:2013
Functional safetyISO 13849-1:2008 (up to category 4/PL e), IEC 61508:2000/IEC 62061:2005 (up to SIL3)
StandardsNFPA 79:2002
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Mechanical specifications
Degree of protectionIP20 (only for use in electrical operating rooms / switch cabinet suitable with minimum protection type IP54)
Connectionscrew terminals
Material
HousingPolyamide PA 66 , black
Mass450 g
MountingDIN rail mounting
Оформить заказ на VAS-2A-K12-U-S1 SIMON вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.