SJ1,8-N-Y16109 x2xG1xxD
Артикул: 106573
Inductive slot sensor
7 839 Р
Производитель:
PEPPERL+FUCHS
Поделиться:
Производитель: PEPPERL+FUCHS
Краткое описание: технические характеристики SJ1,8-N-Y16109 x2xG1xxD
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 2 mm | |
Depth of immersion (lateral) | 4 ... 5 typ. 4.5 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 5000 Hz | |
Hysteresis | 0.3 ... 0.6 mm | |
Current consumption | ||
Measuring plate not detected | min. 4 mA at nominal voltage | |
Measuring plate detected | ≤ 0.65 mA at nominal voltage | |
Functional safety related parameters | ||
MTTFd | 5270 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | flexible leads | |
Housing material | Crastin (PBTB) | |
Degree of protection | IP67 | |
Data for application in connection with hazardous areas | ||
Equipment protection level | Gb , Da , Mb | |
Equipment protection level Gb | ||
Type of protection | intrinsic safety | |
CE marking | [*PD-Z02585A*] | |
Certificates | ||
Appropriate type | SJ1,8-N-Y... | |
ATEX certificate | PTB 99 ATEX 2219 X | |
ATEX marking | II 2G Ex ia IIC T6…T1 Gb | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
IECEx certificate | IECEx PTB 11.0091X | |
IECEx marking | Ex ia IIC T6...T1 Gb | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 30 nF A cable length of 10 m is considered. |
|
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
|
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 67 °C (152.6 °F) T5 : 82 °C (179.6 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW , T6 : 45 °C (113 °F) T5 : 60 °C (140 °F) T4 : 78 °C (172.4 °F) T3 : 78 °C (172.4 °F) T2 : 78 °C (172.4 °F) T1 : 78 °C (172.4 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW , T6 : 30 °C (86 °F) T5 : 45 °C (113 °F) T4 : 57 °C (134.6 °F) T3 : 57 °C (134.6 °F) T2 : 57 °C (134.6 °F) T1 : 57 °C (134.6 °F) |
|
Equipment protection level Da | ||
Type of protection | intrinsic safety | |
CE marking | [*PD-Z02585A*] | |
Certificates | ||
Appropriate type | SJ1,8-N-Y... | |
ATEX certificate | PTB 99 ATEX 2219 X | |
ATEX marking | II 1D Ex ia IIIC T135°C Da | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
IECEx certificate | IECEx PTB 11.0091X | |
IECEx marking | Ex ia IIIC T135°C Da | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 30 nF A cable length of 10 m is considered. |
|
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
|
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 78 °C (172.4 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 57 °C (134.6 °F) |
|
Equipment protection level Mb | ||
Type of protection | intrinsic safety | |
Certificates | ||
Appropriate type | SJ1,8-N-Y... | |
IECEx certificate | IECEx PTB 11.0091X | |
IECEx marking | Ex ia I Mb | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 30 nF A cable length of 10 m is considered. |
|
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
|
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 78 °C (172.4 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 57 °C (134.6 °F) |
|
General information | ||
Use in the hazardous area | see instruction manuals |
Оформить заказ на SJ1,8-N-Y16109 x2xG1xxD вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.