RC10-14-N3 x2xGxxxD
Артикул: 051666
Inductive ring sensor
9 699 Р
Производитель:
PEPPERL+FUCHS
Поделиться:
Производитель: PEPPERL+FUCHS
Краткое описание: технические характеристики RC10-14-N3 x2xGxxxD
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR, bistable | |
Inside diameter | 10 mm | |
Measuring cylinder | ||
Diameter | 2.5 mm | |
Length | 3 mm | |
Measuring cone | ||
Material | 9S20K | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Hysteresis | typ. 1 % | |
Reverse polarity protection | reverse polarity protected | |
Current consumption | ||
Traverse B | 3 mA | |
Traverse A | 1 mA | |
Time delay before availability | ≤ 5 ms | |
Functional safety related parameters | ||
MTTFd | 2144 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -20 ... 100 °C (-4 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.14 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 2G Ex ia IIC T6…T1 Gb The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
Appropriate type | RC10-...-N3... | |
Effective internal capacitance | max. 90 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 120 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 2G |
Оформить заказ на RC10-14-N3 x2xGxxxD вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.
Вам может понравиться