Краткое описание: технические характеристики NCB8-18GM40-N0-OG 123GxxxD
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 8 mm | |
Installation | flush | |
Assured operating distance | 0 ... 6.48 mm | |
Actual operating distance | 7.2 ... 8.8 mm typ. 8 mm | |
Reduction factor rAl | 0.39 | |
Reduction factor rCu | 0.36 | |
Reduction factor r304 | 0.71 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Switching frequency | 0 ... 1500 Hz | |
Hysteresis | 1 ... 15 typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | yes | |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
Current consumption | ||
Measuring plate not detected | min. 2.2 mA | |
Measuring plate detected | ≤ 1 mA | |
Switching state indicator | all direction LED, yellow | |
Functional safety related parameters | ||
MTTFd | 2660 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Electromagnetic compatibility | NE 21:2007 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
UL approval | ||
Ordinary Location | E87056 | |
Hazardous Location | E501628 | |
Control drawing | 116-0452 | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 80 °C (-13 ... 176 °F) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Connection type | cable PUR (halogen-free) , 2 m blue , Oil resistant , Flame-retardant as per IEC 60332-1 Mud-resistant according to IEC61892-4, appendix D Flexible at temperatures as low as -40 °C |
|
Core cross-section | 2x 1 mm2 , black | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Degree of protection | IP66 / IP67 | |
Cable | ||
Bending radius | > 5 x cable diameter | |
Equipment protection level Ga | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
Appropriate type | NCB8-18GM...-N0... | |
Effective internal capacitance | max. 120 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
Appropriate type | NCB8-18GM...-N0... | |
Effective internal capacitance | max. 120 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. | |
Equipment protection level Gc (ic) | ||
Certificate | PF 13 CERT 2895 X | |
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3G Ex ic IIC T6…T1 Gc The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection category "ic" Use is restricted to the following stated conditions |
|
Effective internal capacitance | max. 120 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; A cable length of 10 m is considered. |
|
Special conditions | ||
for Pi=34 mW, Ii=25 mA, T6 | 55 °C (131 °F) | |
for Pi=34 mW, Ii=25 mA, T5 | 55 °C (131 °F) | |
for Pi=34 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) | |
for Pi=64 mW, Ii=25 mA, T6 | 55 °C (131 °F) | |
for Pi=64 mW, Ii=25 mA, T5 | 55 °C (131 °F) | |
for Pi=64 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) | |
for Pi=169 mW, Ii=52 mA, T6 | 41 °C (105.8 °F) | |
for Pi=169 mW, Ii=52 mA, T5 | 41 °C (105.8 °F) | |
for Pi=169 mW, Ii=52 mA, T4-T1 | 41 °C (105.8 °F) | |
for Pi=242 mW, Ii=76 mA, T6 | 29 °C (84.2 °F) | |
for Pi=242 mW, Ii=76 mA, T5 | 29 °C (84.2 °F) | |
for Pi=242 mW, Ii=76 mA, T4-T1 | 29 °C (84.2 °F) | |
Equipment protection level Da | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
Appropriate type | NCB8-18GM...-N0... | |
Effective internal capacitance | max. 120 µF A cable length of 10 m is considered. |
|
Effective internal inductance | max. 50 µH A cable length of 10 m is considered. |
|
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 3G |