General specifications
Switching functionNormally closed (NC)
Output typeTwo-wire
Rated operating distance8 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 6.48 mm ( -25 ... 70 °C (-13 ... 158 °F) )
0 ... 6.08 mm ( -40 ... -25 °C (-40 ... -13 °F) )
Reduction factor rAl 0.49
Reduction factor rCu 0.49
Reduction factor r304 0.74
Output type2-wire
Nominal ratings
Operating voltage3.5 ... 30 V
Switching frequency0 ... 750 Hz
Reverse polarity protectionreverse polarity-conductive
Short-circuit protectionpulsing
Voltage drop≤ 3.5 V
Temperature drift± 15%
Operating current2 ... 100 mA
Off-state current0.4 ... 0.6 mA typ. 0.5 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1930 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialbrass, nickel-plated
Sensing facePBT
Degree of protectionIP67