Технические данные PDF

Краткое описание: технические характеристики  NCB15-30GM50-Z4

General specifications
Switching functionNormally open (NO)
Output typeTwo-wire
Rated operating distance15 mm
Installationflush
Output polarityDC
Assured operating distance0 ... 12 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.4
Reduction factor r304 0.7
Reduction factor rBrass 0.5
Output type2-wire
Nominal ratings
Operating voltage3.5 ... 30 V
Switching frequency500 Hz
Hysteresistyp. 5%
Reverse polarity protectionreverse polarity-conductive
Short-circuit protectionpulsing
Voltage drop≤ 3.5 V
Temperature drift± 15%
Operating current2 ... 100 mA
Off-state currenttyp. 0.8 mA
Switching state indicatorLED, yellow
Pre-fault indicatorLED, red
Stability control-switch point0,8 sr ... 0,9 sr
Functional safety related parameters
MTTFd1390 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.34 mm2
Housing materialbrass, nickel-plated
Sensing facePBT
Degree of protectionIP67