General specifications
Switching functionNormally closed (NC)
Output typePNP
Rated operating distance5 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 3.5 mm
Output type3-wire
Nominal ratings
Installation conditions
B0 mm
C10 mm
F20 mm / 50 mm
Operating voltage10 ... 30 V DC
Switching frequency0 ... 10 Hz
Hysteresis1 ... 10 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 2 V
Operating current0 ... 100 mA
Lowest operating current0 mA
Off-state current0 ... 0.5 mA typ. 0.01 mA
Off-state current TU =40 °C, switching element off≤ 100 µA
No-load supply current≤ 15 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd672 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.14 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP67
Оформить заказ на CBN5-F46-E3 вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.